A valve fire test, also called a fire safe test, checks whether a valve can still seal after being engulfed in a defined flame for a set period. It is the core safety qualification for valves in oil, gas, petrochemical, refining and offshore service. Three standards dominate the market: API 607, API 6FA and ISO 10497 — and choosing the wrong one is one of the most common and most expensive mistakes a valve manufacturer makes.
What a valve fire test actually verifies
During a fire the soft seats and stem packing of a valve are destroyed. A fire-tested valve must still limit leakage in that damaged condition — both through the seat and to atmosphere — and must remain operable so it can be closed to isolate the line. A valve fire test therefore measures three things:
- Through-seat leakage while the valve is burning and again after cooling
- External leakage through body joints, the stem packing and the body-to-bonnet joint
- Operability — the valve must still be cycled during and after the burn
API 607 — quarter-turn valves and soft-seated valves
API 607, currently in its 2022 edition, covers quarter-turn valves (ball, butterfly and plug valves) and other valves with non-metallic seats. The standard burn exposure is 30 minutes with a flame temperature in the range of 760 to 980 °C, followed by a forced cool-down and a post-cooling low-pressure seat test. API 607 is the reference whenever a purchaser specifies a soft-seated quarter-turn valve for flammable service.
API 6FA — pipeline valves and wellhead equipment
API 6FA, currently in its 2026 edition, applies to pipeline valves — gate, globe and check valves — and to wellhead and christmas tree equipment. Its burn curve, burn duration and acceptance leakage rates differ from API 607, and the test is generally regarded as more demanding for larger bore and higher pressure class valves. If your product is a gate valve or part of a wellhead assembly, API 6FA is normally the required standard, not API 607.
ISO 10497 — the international umbrella method
ISO 10497 specifies fire type-testing requirements for valves using a general, internationally recognised method. It is frequently specified in projects outside North America and is the standard buyers fall back on when the supply contract is written to ISO rather than API. Many manufacturers qualify to ISO 10497 alongside API 607 or API 6FA so a single product can serve both markets.
API Spec 6A — wellhead and christmas tree equipment
For wellhead and christmas tree equipment, API Spec 6A contains its own fire design and qualification requirements. Equipment in this category is assessed under API 6FA and/or API Spec 6A, not under API 607.
Which standard do you need?
- Ball, butterfly or plug valve with soft seats → API 607
- Gate, globe or check valve for pipeline service → API 6FA
- Wellhead or christmas tree equipment → API 6FA and/or API Spec 6A
- International or ISO-based project → ISO 10497
- Purchaser named a standard → match the purchase order exactly; never substitute
Testing to the wrong standard produces a certificate the purchaser will reject, so the safe approach is always to qualify to the standard named in the purchase order.
How Valverz runs a valve fire test
- Submit the valve sample with size, pressure class, materials and the target standard
- Confirm the burn curve, burn duration, cooling method and operational test requirements
- Baseline seat test at ambient, then the burn, an operational test during the burn, then post-cooling low and high pressure seat tests
- Receive the third-party valve fire test report and certificate
Send us your sample and applicable standard and we will provide a detailed test plan and quotation within 1 working day. Contact: +86-18731031297 (WeChat available).
Frequently asked questions
Is API 607 the same as ISO 10497?
No. They are separate standards with different scopes, burn curves and acceptance criteria. ISO 10497 is the international umbrella method; API 607 is specific to quarter-turn and soft-seated valves.
Can one fire test cover several sizes of the same valve model?
Most standards allow a qualification to be extended to a range of sizes and pressure classes based on a tested representative sample, but the exact rules differ between API 607, API 6FA and ISO 10497. Confirm the qualification range before you plan your sample set.
How long does a valve fire test take?
Standard lead time for one sample is 1 to 2 weeks including test execution and report preparation; expedited service is available on request.